Status, Commands – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 154
154
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Chapter 7
Logic Functions
Semantics of selections:
•
Last-state = hold the output in its last state on communication loss
•
De-energize = put output into de-energized or normal state on
communication loss
•
Resume = restore output control when communication recovers
•
Freeze = maintain state of output when communication recovers until one
of the following occurs:
–
Logic controller enters program mode
–
Power cycle to the power monitor
–
Change the parameter value to ‘resume’
•
Local Control = Revert to local power monitor control (pulsed or
setpoint) on communication loss. When communication recovers and
connection is re-established, output control by the connection host
resumes.
Status
Relay and KYZ output status is reported by the state of the following Boolean
tags, found in the
table. For each tag, 0 = False, 1 = True.
KYZ _Output_Energized
KYZ_Forced_On
KYZ_Forced_Off
Relay_1_Output_Energized
Relay_1_Forced_On
Relay_1_Forced_Off
Relay_2_Output_Energized
Relay_2_Forced_On
Relay_2_Forced_Off
Relay_3_Output_Energized
Relay_3_Forced_On
Relay_3_Forced_Off
Commands
The following command parameters are found in the
table. These commands are not permitted if an
Exclusive Owner connection has been established with a Logix controller.
Command Word 1