Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 272
272
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
35
Int16
Logic Level 1
Gate 8 Function
Selects the logic type
0 = disabled
1 = AND
2 = NAND
3 = OR
4 = NOR
5 = XOR
6 = XNOR
IMPORTANT: XOR and XNOR use Inputs 1 and 2 only.
0
0…6
36
Int16
L1_G8 Input 1
Selects the first input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
…
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0
-20…20
37
Int16
L1_G8 Input 2
Selects the second input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
…
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0
-20…20
38
Int16
L1_G8 Input 3
Selects the third input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
…
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0
-20…20
39
Int16
L1_G8 Input 4
Selects the fourth input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
…
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0
-20…20
40
Int16
Logic Level 1
Gate 9 Function
Selects the logic type
0 = disabled
1 = AND
2 = NAND
3 = OR
4 = NOR
5 = XOR
6 = XNOR
IMPORTANT: XOR and XNOR use Inputs 1 and 2 only.
0
0…6
Table 70 - Configuration.Setpoint_Logic Data Table
Element
Number
Type
Tag Name
Description
Default
Range