beautypg.com

Loggingresults.waveform_log (m6 model) – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 351

background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

351

PowerMonitor 5000 Unit Data Tables

Appendix A

LoggingResults.Waveform_Log (M6 model)

Table 175 - Table Properties

CIP Instance Number

871

PCCC File Number

F80

No. of Elements

43

Length in Words

86

Data Type

Real

Data Access

Read Only

Table 176 - LoggingResults. Waveform_Log Data Table

Element
Number

Type

Tag Name

Description

Unit

Range

0

Real

Record_Indicator

Indicates the significance of the data in the record

0 = No record returned
1= the record contains
parameter values
2 = the record contains
general information of
the log file being
retrieved, reference to
each item description in
the data table
3 = log file not found.

1

Real

Timestamp_Date

Date of cycle collection MMDDYY

MMDDYY

0…123199

2

Real

Timestamp_Time

Time of cycle collection hhmmss

hhmmss

0…235959

3

Real

Microsecond_Stamp

Microsecond of cycle collection

uS

0.000…999999

4

Real

File_ID

The selected file ID

#

1…256

5

Real

Total_Cycles

Total cycles of the waveform file

#

0…3640

6

Real

Cycle_Returned

The current returned cycle

#

0…(Total cycles - 1)

7

Real

Frequency

The frequency of average cycle

Hz

40.0 … 75.0

8

Real

Mag_Angle

The returned value is mag or angle

#

0 = Mag, 1 = Angle

9

Real

Channel

The channel returned

#

0 = V1
1 = V2
2 = V3
3 = V4
4 = I1
5 = I2
6 = I3
7 = I4

10

Real

Order

The range of harmonic orders of returned values

#

0 = DC…31st (M6)