Loggingresults.waveform_log (m6 model) – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 351
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
351
PowerMonitor 5000 Unit Data Tables
Appendix A
LoggingResults.Waveform_Log (M6 model)
Table 175 - Table Properties
CIP Instance Number
871
PCCC File Number
F80
No. of Elements
43
Length in Words
86
Data Type
Real
Data Access
Read Only
Table 176 - LoggingResults. Waveform_Log Data Table
Element
Number
Type
Tag Name
Description
Unit
Range
0
Real
Record_Indicator
Indicates the significance of the data in the record
0 = No record returned
1= the record contains
parameter values
2 = the record contains
general information of
the log file being
retrieved, reference to
each item description in
the data table
3 = log file not found.
1
Real
Timestamp_Date
Date of cycle collection MMDDYY
MMDDYY
0…123199
2
Real
Timestamp_Time
Time of cycle collection hhmmss
hhmmss
0…235959
3
Real
Microsecond_Stamp
Microsecond of cycle collection
uS
0.000…999999
4
Real
File_ID
The selected file ID
#
1…256
5
Real
Total_Cycles
Total cycles of the waveform file
#
0…3640
6
Real
Cycle_Returned
The current returned cycle
#
0…(Total cycles - 1)
7
Real
Frequency
The frequency of average cycle
Hz
40.0 … 75.0
8
Real
Mag_Angle
The returned value is mag or angle
#
0 = Mag, 1 = Angle
9
Real
Channel
The channel returned
#
0 = V1
1 = V2
2 = V3
3 = V4
4 = I1
5 = I2
6 = I3
7 = I4
10
Real
Order
The range of harmonic orders of returned values
#
0 = DC…31st (M6)
1 = 32nd…63rd (M6)