Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 261
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
261
PowerMonitor 5000 Unit Data Tables
Appendix A
13
Real
Hysteresis 12
The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0
0…10,000,000
14
Real
Assert Delay
Seconds 12
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0
0.000…3600
15
Real
Deassert Delay
Seconds 12
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0
0.000…3600
16
Real
Parameter
Selection 13
Selection of the input parameter from the
Setpoint Parameter Selection List
0
0…105
17
Real
Input Reference
Selection 13
Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value
0
0
18
Real
Test Condition 13
0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0
0…3
19
Real
Evaluation Type
13
0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
0
0…3
20
Real
Threshold 13
The value, percent, or state that triggers the output action.
0
-10,000,000…
10,000,000
21
Real
Hysteresis 13
The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0
0…10,000,000
22
Real
Assert Delay
Seconds 13
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0
0.000…3600
23
Real
Deassert Delay
Seconds 13
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0
0.000…3600
24
Real
Parameter
Selection 14
Selection of the input parameter from the
Setpoint Parameter Selection List
0
0…105
25
Real
Input Reference
Selection 14
Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value
0
0
26
Real
Test Condition 14
0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0
0…3
27
Real
Evaluation Type
14
0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
0
0…3
28
Real
Threshold 14
The value, percent, or state that triggers the output action.
0
-10,000,000…
10,000,000
29
Real
Hysteresis 14
The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0
0…10,000,000
30
Real
Assert Delay
Seconds 14
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0
0.000…3600
31
Real
Deassert Delay
Seconds 14
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0
0.000…3600
Table 66 - Configuration.Setpoints_11_15 Data Table
Element
Number
Type
Tag Name
Description
Default
Range