Setup, Time zones – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 176

176
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Chapter 8
Other Functions
Setup
The Network Time Synchronization set-up parameters for SNTP and PTP are
found in the
Configuration.Communications_Native
table.
Time Zones
Parameter
Description
Range
Default
Time_Sync_Source
Selection for Time Sync
0 = Disable
1 = SNTP
2 = PTP (IEEE 1588)
0…2
2
SNTP_Mode_Select
0 = Unicast
1= Anycast Mode
The SNTP address is a broadcast address of an anycast group
0…1
0
SNTP_Update_Interval
Number of seconds before next update
1…32766
300
SNTP_Time_Zone
The time zone in which the power monitor is located
0…32
6 (Central Time)
SNTP Time Server IP
Unicast server or anycast group IP address in format aaa.bbb.ccc.ddd
0.0.0.0…255.255.255.255
0.0.0.0
QOS_DSCP_Enable
0 = Disable
1 = Enable
0…1
1
QOS_DSCP_PTP_Event
PTP (IEEE 1588) event messages
0…63
59
QOS_DSCP_PTP_General
PTP (IEEE 1588) general messages
0…63
47
QOS_DSCP_Urgent
CIP transport class 0/1 messages with Urgent priority
0…63
55
QOS_DSCP_Scheduled
CIP transport class 0/1 messages with Scheduled priority
0…63
47
QOS_DSCP_High
CIP transport class 0/1 messages with high priority
0…63
43
QOS_DSCP_Low
CIP transport class 0/1 messages with low priority
0…63
31
QOS_DSCP_Explicit
CIP UCMM CIP class 3
0…63
27
Table 31 - Time Zone Information
Value
Offset
from GMT
Time Zone Name
Areas in Time Zone
0
GMT-12:00
Dateline Standard Time
Eniwetok, Kwajalein
1
GMT-11:00
Samoa Standard Time
Midway Island, Samoa
2
GMT-10:00
Hawaiian Standard Time
Hawaii
3
GMT-09:00
Alaskan Standard Time
Alaska
4
GMT-08:00
Pacific Standard Time
Pacific Time (US & Canada,; Tijuana)
5
GMT-07:00
Mountain Standard Time
Mountain Time (US & Canada)
US Mountain Standard Time
Arizona
6
GMT-06:00
Canada Central Standard Time
Saskatchewan
Central America Standard Time
Central America
Central Standard Time
Central Time (US & Canada)
Mexico Standard Time
Mexico City