Setpoint logic gate setup, Setpoint output setup – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 163

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
163
Logic Functions
Chapter 7
Relative_Setpoint_Interval_m
This tag, found in the
table, defines the length of
the sliding average interval used in all setpoints with Percent of Sliding Reference
evaluation type. Range: 1 (default)…1440 minutes
Setpoint Logic Gate Setup
The tags listed below can be used to configure setpoint logic gates and are found
in the
Configuration.Setpoint_Logic Data Table
.
Logic Level 1 Gate n Function
Selects the logic type for the gate. These are the choices:
0 = disabled
1 = AND
2 = NAND
3 = OR
4 = NOR
5 = XOR
6 = XNOR
L1_Gn Input 1
L1_Gn Input 2
L1_Gn Input 3
L1_Gn Input 4
Selects input parameters for the nth logic gate (n = 1 … 10). Each AND, NAND,
OR, and NOR gate has up to four inputs. These are the choices:
0 = Disabled
1 = Setpoint 1; -1 = Setpoint 1 inverted
2 = Setpoint 2; -2 = Setpoint 2 inverted
3 = Setpoint 3; -3 = Setpoint 3 inverted
…
20 = Setpoint 20; -20 = Setpoint 20 inverted
Setpoint Output Setup
The tags listed below can be used to optionally tie output actions to setpoints,
and are found in the
Configuration.Setpoint_Outputs
table.
IMPORTANT
XOR and XNOR use Inputs 1 and 2; both must be configured at the same time,
otherwise an error is reported and the logic gate configuration is rejected.