Configuration parameter object table – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 238
238
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
Configuration Parameter Object Table
Table 45 - Table Properties
CIP Class Code
0x0F
No. of Parameters
52
Data Type
Varies
Data Access
Read/Write
TIP
Configuration.Instance Data Table
for descriptions of each
parameter.
Table 46 - Configuration Parameter Object Table
Instance Number
Parameter Object Name
Type
Units
Range
Default Value
1
Metering_Mode
Real
N/A
0…9
2
2
V1_V2_V3_PT_Primary
Real
V
0 …1,000,000
480
3
V1_V2_V3_PT_Secondary
Real
V
0…690
480
4
I1_I2_I3_CT_Primary
Real
A
0…1,000,000
5
5
I1_I2_I3_CT_Secondary
Real
A
5
5
6
VN_PT_Primary
Real
V
0 …1,000,000
480
7
VN_PT_Secondary
Real
V
0…690
480
8
I4_CT_Primary
Real
A
0…1,000,000
5
9
I4_CT_Secondary
Real
A
5
5
10
Nominal_System_LL_Voltage
Real
V
0…1,000,000
480
11
Reserved
Real
N/A
0…0
0
12
Nominal_System_Frequency
Real
Hz
50…60
60
13
Realtime_Update_Rate
Real
N/A
0…3
0
14
Date_Year
Int16
Year
2010…2100
2010
15
Date_Month
Int16
Mon
1…12
1
16
Date_Day
Int16
Day
1…31
1
17
Time_Hour
Int16
Hour
0 …23
0
18
Time_Minute
Int16
Min
0…59
0
19
Time_Seconds
Int16
Sec
0…59
0
20
Time_Milliseconds
Int16
Mise
0…999
0
21
Unit_Error_Action
Int16
N/A
0…1
1
22
Energy_Log_Interval
Int16
N/A
-1…60
15
23
Energy_Log_Mode
Int16
N/A
0…1
1
24
Time_Of_Use_AutoStore
Int16
N/A
0…31
31
25
Demand_Source
Real
N/A
0… 3
0
26
Demand_Period_Length
Real
N/A
0…99
15
27
Number_Demand_Periods
Real
N/A
1…15
1
28
Forced_Demand_Sync_Delay
Real
N/A
0…900
10