Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 249
![background image](/manuals/578319/249/background.png)
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
249
PowerMonitor 5000 Unit Data Tables
Appendix A
7
Real
KYZ_Solid_State_Output_Scale
The KYZ output parameter divided by the scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.
1,000
1…
100,000
8
Real
KYZ_Pulse_Duration_Setting
Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: The value for delay is rounded off to the nearest 10 ms internally during
this function.
250 (ms)
0 or 50
…1000
9 Real
Output_Relay_1_Output_
Parameter
The parameter selected pulses the relay 1 output at a rate that equals the parameter
value divided by relay 1 scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
0
0…6
10 Real
Output_Relay_1_Output_Scale
The relay 1 output parameter divided by the relay 1 scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.
1,000
1…
100,000
11 Real
Output_Relay_1_Pulse_Duration_
Setting
Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: The value for delay is rounded off to the nearest 10 ms internally during
this function.
250 (ms)
0 or 50
…1000
12 Real
Output_Relay_2_Output_
Parameter
The parameter selected pulses the relay 2 output at a rate that equals the parameter
value divided by relay 2 scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
0
0…6
13 Real
Output_Relay_2_Output_Scale
The relay 2 output parameter divided by the relay 2 scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.
1,000
1…
100,000
14 Real
Output_Relay_2_Pulse_Duration_
Setting
Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: the value for delay is rounded off to the nearest 10 ms internally during
this function.
250 (ms)
0 or 50
…1000
15 Real
Output_Relay_3_Output_Paramet
er
The parameter selected pulses the relay 3 output at a rate that equals the parameter
value divided by relay 3 scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
0
0…6
16 Real
Output_Relay_3_Output_Scale
The relay 3 output parameter divided by the relay 3 scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.
1,000
1…
100,000
17 Real
Output_Relay_3_Pulse_Duration_
Setting
Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: the value for delay is rounded off to the nearest 10ms internally during
this function.
250 (ms)
0 or 50
…1000
Table 56 - Configuration.System.General Data Table
Element
Number
Type
Tag Name
Description
Default
Range