Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 259
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
259
PowerMonitor 5000 Unit Data Tables
Appendix A
32
Real
Parameter
Selection 10
Selection of the input parameter from the
Setpoint Parameter Selection List
0
0…105
33
Real
Input Reference
Selection 10
Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value
0
0
34
Real
Test Condition 10
0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0
0…3
35
Real
Evaluation Type
10
0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
0
0…3
36
Real
Threshold 10
The value, percent, or state that triggers the output action.
0
-10,000,000…
10,000,000
37
Real
Hysteresis 10
The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0
0…10,000,000
38
Real
Assert Delay
Seconds 10
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0
0.000…3600
39
Real
Deassert Delay
Seconds 10
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0
0.000…3600
40…49
Real
Reserved
Future Use
0
0
Table 64 - Configuration.Setpoints_6_10 Data Table
Element
Number
Type
Tag Name
Description
Default
Range