Status.general – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 291

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
291
PowerMonitor 5000 Unit Data Tables
Appendix A
Status.General
Table 101 - Table Properties
CIP Instance Number
823
PCCC File Number
N32
No. of Elements
55
Length in Words
55
Data Type
Int16
Data Access
Read Only
Table 102 - Status.General Data Table
Element
Number
Type
Tag Name
Description
Range
0
Int16
Bulletin_Number
1426
0 or 1426
1
Int16
Device_Class
Describes the product device type.
5 = PM_PowerMonitor 5000
5
2
Int16
Model
Indicates the feature set included in the catalog number.
1 = M5
2 = M6
1 or 2
3
Int16
Communication_Options
Displays the communication hardware options.
0 = NAT (Native Ethernet)
1 = CNT (Optional ControlNet)
3 = DNT (Optional DeviceNet)
0, 1, 3
4
Int16
Nominal_Input_Current
5 = 5 Ampere
5
5
Int16
Metering_Class_Designation
Designation for the metering accuracy.
2 = Class Designation 0.2
2
6
Int16
Series_Letter
The current hardware revision. A…Z.
0…26
7
Int16
Manufacture_Month
Month the Unit was manufactured.
1…12
8
Int16
Manufacture_Day
Day the Unit was manufactured.
1…31
9
Int16
Manufacture_Year
Year the Unit was manufactured.
2010…2100
10
Int16
Overall_System_Status
Reports the overall system status of each system assembly.
0 = Status PASS
Bit 0 = 1: Assembly_Slot_0_inst_1_Error
Bit 1 = 1: Assembly_Slot_0_inst_2_Error
Bit 2 = 1: Assembly_Slot_1_inst_1_Error
Bit 3 = 1: Assembly_Slot_1_inst_2_Error
Bit 4 = 1: Assembly_Slot_2_inst_1_Error
Bit 5 = 1: Assembly_Slot_2_inst_2_Error
Bit 6 = 1: Assembly_Slot_3_inst_1_Error
Bit 7 = 1: Assembly_Slot_3_inst_2_Error
For the detailed error code, please refer to Status_RunTime Table.
0…65,535
11
Int16
Error_Log_Contents
Number of records in the Error Log.
0…65,535
12
Int16
Metering_Configuration_Locked
The hardware switch for configuration is locked.
0…1
13
Int16
PTP_Status
Indicates PTP status
0 = PTP Listening
1 = PTP Slave
2 = PTP Master
0…2
14…54
Int16
Reserved
Future Use.
0