Powerquality.harmonics_results (m6 model) – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 355
![background image](/manuals/578319/355/background.png)
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
355
PowerMonitor 5000 Unit Data Tables
Appendix A
PowerQuality.Harmonics_Results (M6 model)
Table 179 - Table Properties
CIP Instance Number
860
PCCC File Number
F69
No. of Elements
37
Length in Words
74
Data Type
Real
Data Access
Read Only
Table 180 - PowerQuality.Harmonics_Results Data Table
Element
Number
Type
Tag Name
Description
Units
Range
0
Real
Metering_Date_Sta
mp
Date of cycle collection MM:DD:YY
MMDDYY
0…123199
1
Real
Metering_Time_Sta
mp
Time of cycle collection hhmmss
hhmmss
0…235959
2
Real
Metering_Microseco
nd_Stamp
Microsecond of cycle collection
uS
0.000…999999
3
Real
Channel
Indicates the channel selected in the most recent write of Table
Configuration.Harmonics_Optional_Read
0 = No Selection
1 = V1-N RMS
2 = V2-N RMS
3 = V3-N
4 = VN-G RMS
5 = V1-V2 RMS
6 = V2-V3 RMS
7 = V3-V1 RMS
8 = I1 RMS
9 = I2 RMS
10 = I3 RMS
11 = I4 RMS
12 = L1 kW RMS
13 = L2 kW RMS
14 = L3 kW RMS
15 = L1 kVAR RMS
16 = L2 kVAR RMS
17 = L3 kVAR RMS
18 = L1 kVA RMS
19 = L2 kVA RMS
20 = L3 kVA RMS
21 = Total kW RMS
22 = Total kVAR RMS
23 = Total kVA RMS
24 = V1-N Angle
25 = V2-N Angle
26 = V3-N Angle
27 = VN-G Angle
28 = V1-V2 Angle
29 = V2-V3 Angle
30 = V3-V1 Angle
31 = I1 Angle
32 = I2 Angle
33 = I3 Angl
34 = I4 Angle
1…34
4
Real
Order
Selected harmonics order range.
0 = DC…31st
1 = 32nd…63rd
0…1
(M6)