Order Parameter
1

k

1

= 1 - β

2

α

α

β

=

1

1

2

k

3

k

3

= 0

4

k

4

= 0

For a single pole,

p

s

s

+

parameters are

pT

e

=

=

β

α

,

0

.

Example:
A filter consists of one second-order block and one first-order block. The second-order
block is a notch filter with a 300-Hz notch frequency and a damping of 0.14. The sample
time is 360 microseconds. The discrete equivalent of the filter is parameterized by:
k1 = 0.3372, k2 = 0.4573, k3 = -0.7277 and k4 = 0.5222.

The second block is a simple pole with a 400-Hz frequency. It may be represented by:
k1 = 0.1341, k2 = 0, k3 = 0 and k4 = 0.

The KV parameter vector should be programmed as follows:

Parameter Value

Description

KV[0] 100

KV[1]

12

Last index used

KV[2]

16

First block, non-scheduled

KV[3]

IQ25(0.3372)

Parameter 1 (k1)

KV[4]

IQ25 (0.4573)

Parameter 2 (k2)

KV[5]

IQ25 (-0.7277)

Parameter 3 (k3)

KV[6]

IQ25 (0.5222)

Parameter 4 (k4)

KV[7]

16

Second block, non-scheduled

KV[8]

IQ25 (0.1341)

Parameter 1 (k1)

KV[9]

0

Parameter 2 (k2)

KV[10]

0

Parameter 3 (k3)

KV[11]

0

Parameter 4 (k4)

The value of KV[N] parameters for N = 12…47 is not important.

Above, IQ25(x) simply means

25

(2

)

round

x

.

Be aware that the KV[N] manual programming is not required because the Composer
program performs it manually.