IAI America XSEL-S User Manual
Page 88
![background image](/manuals/350292/88/background.png)
4. RC Gateway Function setting
82
[Procedure 6]
Parameter Writing
Write the edited operation mode setting parameters to MSCON. Click on the
Write
button shown below and a confirmation window pops up. Click on the
Yes button.
If the writing is finished in normal condition, writing complete window appears. Click
OK.
[Procedure 7] MSCON Re-start
A confirmation window for Gateway Unit reboot opens. Click “Yes” to accept the reboot.
[Procedure 8] Confirmation of Written Parameters
After rebooting, a confirmation window for parameter reading appears for confirmation of
the written contents.
Once the reading process is complete, confirm that the written contents are reflected.
If the writing process is not completed properly, have the setting complete again from
Step 1.
When the confirmation is done, end the Gateway Parameter Setting Tool.