4. RC Gateway Function setting

50

[Procedure 3] Setting of number of used positions (Set this only in method to use position data in X-SEL)

Set the number of positions to be used and the maximum value of the axis number for

when using the position data in X-SEL.

No.

I/O Parameter

Unit

Set Value

Default

factory setting

501 Number of RC Gateway

Position Data

-

1to 512

0

502

Maximum Axis Number for RC

Gateway Position Data

Definition

-

0to 15

0

503

Number of Position Data for RC

Gateway Position Data

Definition

-

1to 512

0

(1) I/O Parameter No.501

Input the number of positions of the axis that has the most positioning points among the

connected axes. However, there is a restriction to the maximum number of positions for each

axis depending on the number of connected axes. Have the setting done by referring to the

following.

Number of connected axes

Number of positions (per axis)

0 to 7

512

8

455

9

409

10

372

11

341

12

315

13

292

14

273

15

256

(2) I/O Parameter No.502

Input the maximum value of the used axis number.

(3) I/O Parameter No.503

Input the same value as that in No. 501.

* Go ahead to Section 4.2 for SIO type and 4.3 for Fieldbus type.