2. Specification
25
2.2.4 Input and Output Timing (Fieldbus Type)
The response time (Time it takes RC controller to respond back to XSEL controller's query) can be
calculated by the formula below:
Response time [msec] = Yt + Xt + 2 × (Ft + Mt) + Command processing time
Yt : SEL Program ĺ RC Controller transmission delay time… 2ms or more (It may increase due to
number of executed SEL programs or
number of effective axes.)
Xt : RC Controller ĺ SEL Program transmission delay time… 2ms or more (It may increase due to
number of executed SEL programs or
number of effective axes.)
Ft : Fieldbus Link Cycle Time
x
In the case that the Multi-axis (MSEP or MSCOM) units only are connected:
Ft = Ȉ {0.316 + 0.076 × (T
HBYTE
+ T
ABYTE
× Ni)} + 1.0
Ȉ : Total No. of the controller connected multi-axis (MSEP or MSCOM) units
(= No. of Connected Nodes)
T
HBYTE
: Number of header domain bytes. Fixed to 16
T
ABYTE
: Number of bytes for each axis.16 for method to use position data in X-SEL, and 8 for
method to use position data in RC
Ni : No. of connected axes of the multi-axis (MSEP or MSCOM) units per controller
x
When connecting only CON single axis (A/PCON, SCON-CA)
Ft = 1.532 × N + 1.0 (Method to use position data in X-SEL)
Ft = 0.556 × N + 1.0 (Method to use position data in RC)
N : Number of connected nodes (= number of connected axes)
Mt : Modbus Line Time (Added only for MSEP or MSCOM): 10ms
Caution : x Regarding the response time of Fieldbus Type, because the communication data
length of DeviceNet is 8 bytes, the communication speed becomes slow if the
number of communication bytes for each node exceeds 8 bytes. For instance,
even though the communication size in the method to use the position data in RC
is 80 bytes for input and output, for MSEP (8-axis connection: 1 node), it is 20
[ms], but for CON single axis (10-axis connection: 10 nodes), it iis 9 [ms].
x
Yt increases with the facts such as the number of SEL programs executed at the
same time or the number of effective axes in the RC Gateway Funciton.
x
When a communication error is generated, the Fieldbus Link Time Ft and Modbus
Link Time Mt may be longer since such actions as a retry will take place.