2. Specification

25

2.2.4 Input and Output Timing (Fieldbus Type)

The response time (Time it takes RC controller to respond back to XSEL controller's query) can be

calculated by the formula below:

Response time [msec] = Yt + Xt + 2 × (Ft + Mt) + Command processing time

Yt : SEL Program ĺ RC Controller transmission delay time… 2ms or more (It may increase due to

number of executed SEL programs or

number of effective axes.)

Xt : RC Controller ĺ SEL Program transmission delay time… 2ms or more (It may increase due to

number of executed SEL programs or

number of effective axes.)

Ft : Fieldbus Link Cycle Time

x

In the case that the Multi-axis (MSEP or MSCOM) units only are connected:

Ft = Ȉ {0.316 + 0.076 × (T

HBYTE

+ T

ABYTE

× Ni)} + 1.0

Ȉ : Total No. of the controller connected multi-axis (MSEP or MSCOM) units

(= No. of Connected Nodes)

T

HBYTE

: Number of header domain bytes. Fixed to 16

T

ABYTE

: Number of bytes for each axis.16 for method to use position data in X-SEL, and 8 for

method to use position data in RC

Ni : No. of connected axes of the multi-axis (MSEP or MSCOM) units per controller

x

When connecting only CON single axis (A/PCON, SCON-CA)

Ft = 1.532 × N + 1.0 (Method to use position data in X-SEL)

Ft = 0.556 × N + 1.0 (Method to use position data in RC)

N : Number of connected nodes (= number of connected axes)

Mt : Modbus Line Time (Added only for MSEP or MSCOM): 10ms

Caution : x Regarding the response time of Fieldbus Type, because the communication data

length of DeviceNet is 8 bytes, the communication speed becomes slow if the

number of communication bytes for each node exceeds 8 bytes. For instance,

even though the communication size in the method to use the position data in RC

is 80 bytes for input and output, for MSEP (8-axis connection: 1 node), it is 20

[ms], but for CON single axis (10-axis connection: 10 nodes), it iis 9 [ms].

x

Yt increases with the facts such as the number of SEL programs executed at the

same time or the number of effective axes in the RC Gateway Funciton.

x

When a communication error is generated, the Fieldbus Link Time Ft and Modbus

Link Time Mt may be longer since such actions as a retry will take place.