7 example 7 - using text and text attributes to, Indicate conditions – Micromod Micro-PWC: 53PW6000 MicroPWC Configuration Guide User Manual
Page 164
Micro-PWC CONFIGURATION GUIDE
144 Grafx Editor
4.3.4.7 Example 7 - Using Text and Text Attributes to Indicate Conditions
Process Conditions:
Switches on a tank indicating High Level (LI101HL.OUT) and High High Level (LI101HHL.OUT) are used
to indicate alarm conditions.
Objective:
Display a text message on a graphic to indicate the condition of these switches, using the parameters in
the following table:
Procedure:
1.
Put a text object on a Graphic.
2.
Position the pointer over the object, then click the right mouse button. Select the Dynamic
Attributes item from the resulting pop-up menu. The Expression Dynamics window will appear.
3.
Configure the expression and settings from the two tables below.
Input Condition
Text
Color
LI101HL.OUT = 0 and LI101HHL.OUT = 0
Normal
Green
LI101HL.OUT = 1 and LI101HHL.OUT = 0
Hi Level
Yellow
LI101HL.OUT = 1 and LI101HHL.OUT = 1
Hi Hi Level
Red
LI101HL.OUT = 0 and LI101HHL.OUT = 1
Unknown
White Flash
NUMBER
EXPRESSION
TRUE SETTINGS
FALSE
SETTINGS
1
LI101HL.OUT == 0 && LI101HHL.OUT == 1
Blink (See Below)
None
2
LI101HL.OUT == 0 && LI101HHL.OUT == 0
text = Normal
text color = 2
None
3
LI101HL.OUT == 1 && LI101HHL.OUT == 0
text = Hi Level
text color = 3
None
4
LI101HL.OUT == 1 && LI101HHL.OUT == 1
text = Hi Hi Level
text color = 1
None
5
LI101HL.OUT == 0 && LI101HHL.OUT == 1
text = Unknown
text color = 7
None
Blink Configuration (For Expression 1)
PERIOD
PHASE
BLINK
COLOR 1
DURATION 1
BLINK
COLOR 2
DURATION 2
STEADY
COLOR
2
1
7
1
0
1
0