RISCO Group LightSYS 2 User Manual
Page 77

Installer Programming
Page 77
Quick Keys
Parameter
Default
Range
Arm Pre‐Warning
No
Yes/No
Related to auto arm/disarm operation.
YES: For any partition(s) set up for auto arming, an audible exit delay
(warning) countdown will commence 4.25 minutes prior to the
automatic arming. During this period, exit delay beeps will be heard.
You can enter a valid user code at any time during the countdown to
delay the partition’s automatic arming by 45 minutes.
When an “Auto‐Arm” partition is disarmed, as described above, it can
no longer be automatically armed during the current day.
The extended 4.25 minutes warning does not apply to automatic partial
arming.
NO: Auto arming for any programmed partition(s) takes place at the
designated time. The programmed exit delay period and any audible
signal occur as expected.
Advanced
Yes
Yes/No
This section refers to the advanced controls in the system.
Double Verification
of Fire Alarms
No
Yes/No
YES: Implemented on detection of smoke or fire for verification. Power
to the smoke detector(s) in the affected zone is cut off and restored after
the time defined in the Switch Aux Break delay (page 71). If a
subsequent detection occurs in the same zone within one minute of the
first detection, the system emits a fire alarm.
NO: No fire alarm verification takes place.