RISCO Group LightSYS 2 User Manual
Page 128

Installer Programming
Page 128
Quick Keys
Parameter
Switched Aux
Activates the utility output when a fire zone is activated (for fire
detection) according to the time defined in double verification of fire
alarms, page 7777.
This utility output will not have the option to choose pulse or latch in
the Utility Output: Code. The pulse time is defined in switched
auxiliary break, page 71.
GSM Error
Relates to GSM/GPRS module. Activates the utility output in the
following cases:
There is no SIM card in the GSM/GPRS BUS Module or SIM is
faulty
GSM RSSI signal level is low
GSM network fault
Bell Test
Activates the output when the “Bell Test” option is selected and
deactivates when the “Bell Test” option is finished.
Installation
Activates the output following the system installation status. It activates
when the system is in installer programming mode and deactivates
when exiting installer’s mode.
Walk Test
Activates the output when the “Walk Test” option is selected and
deactivates when the “Walk Test” option is finished.
Burglary
Activates the output (Pulsed only) following any intruder activation in
the system (Regardless the bell time out timer). The maximum number
of times an output can be activated from the same zone is defined
according to the Swinger Limit Timer (Quick key
)