RISCO Group LightSYS 2 User Manual
Page 109
Installer Programming
Page 109
Quick Keys
Parameter
Default
Range
ZZ
Auxiliary Relay Mode
Off
Defines the operation of the auxiliary relay of the detector.
OFF
‐ Auxiliary relay is disabled
24 Hours ‐ The auxiliary relay will always follow an alarm
NIGHT ONLY ‐ The auxiliary relay output will follow an alarm
condition only during night time. The time defined by the photocell on
the PCB.
ZZ
Auxiliary Relay Time
2.2 Seconds 2.2–480 seconds
Defines the time duration that the auxiliary relay is activated.
2.2 SECONDS 2 MINUTES 4 MINUTES 8 MINUTES
Bus Zone: iWISE DT Grade 2
Quick Keys
Parameter
Default
Range
ZZ
LEDS
On
Defines the LEDS operation mode.
OFF ‐ Disables the LEDS operation.
ON
– Enables the LEDS operation.
ZZ
MW (Microwave) Range
Trimmer
Defines the microwave channel range.
MINIMUM 25% 50% 65% 85% MAXIMUM TRIMMER
(MW is defined by the trimmer setting on the PCB)
ZZ
ACT
No
Defines the Anti‐Cloak™ Technology (ACT) operation mode.
NO – Disables the ACT mode
YES – Enables the ACT mode
ZZ
Automatic Microwave Bypass
No
Defines whether the MW channel will be bypassed or not while the
detector identifies trouble in the MW channel.
NO ‐ While detecting a problem in the MW channel it is not bypassed.
Alarm condition cannot be established until the MW channel is fixed.
YES ‐ Switches the detector to operate only in PIR mode in case of
MW trouble