RISCO Group LightSYS 2 User Manual
Page 122

Installer Programming
Page 122
If a zone in the Soak Test list has an alarm during the 14‐day period, the
keypad indicates to the user that the test has failed. After the user looks at
the View Trouble option (described in the LightSYS2 User’s Manual), the
trouble message will be erased. This will be indicated in the event log, but
no alarm will be generated. The alarmed zone’s 14‐day Soak Test period
is then reset and restarted..
To set up a Soak‐Test. [LightSYS]
1. From the Install menu, press quick keys
. The
following display appears:
ZONES FOR TEST:
01) ZONE 01 N
2. To put a zone on Soak Test, press
. The following display
appears:
LOCATION 01:
ZONE: 00-32
3.
Press the keys as per the zone number (e.g. 01 for zone 1)
4. Press
to confirm and display the initial menu.
5. To add a second zone for Soak Test, press and repeat the
procedure above, ‐OR Press the
key to return to the
previous menu.
Cross Zones
Default: No cross zoning
The Zone Crossing menu is used for additional protection from false alarms and contains
parameters that enable you to link together two related zones. Both must be violated within a
designated time period (between 1 and 9 minutes) before an alarm occurs.
This type of linking is used with motion detectors in hostile or false‐alarm prone environments.
The LightSYS2 allows 10 unique sets of zone links (pairs of zones), which can be manually
specified, as required. Zones crossed with themselves are valid pairs. They need to register a
violation twice to trigger the alarm. This process is known as Double Knock. You may want to
establish a number of zone links, but leave them deactivated at this time (see below).