beautypg.com

RISCO Group LightSYS 2 User Manual

Page 103

background image

Installer Programming

Page 103

Quick Keys

Parameter

Default

Range



ZZ

 

Tamper  

 

 

For tamper detection. This zone operates the same as 24 hours zone, but 
it has a special reporting code.  

Note:

For this zone type the zone sound is determined according to the 
Tamper Sound defined under 1) System 4) Sound  1) Tamper 



ZZ

 

Technical

 

 

This zone operates the same as 24 hours zone, its report code should be 
manually set according to the relevant detector connected to the zone. 



ZZ

 

Water

 

 

For flood or other types of water detectors. This zone operates the same 
as 24 hours zone, but it has a special flood report code.  



ZZ

 

Gas

 

 

For Gas (natural gas) leak detector. This zone operates the same as 24 
hours zone, but it has a special gas report code.  



ZZ

 

CO

 

 

For CO (Carbon Monoxide) gas detectors. This zone operates the same 
as 24 hours zone, but it has a special CO report code.  



ZZ

 

Exit Term

 

 

This type of zone is used to avoid a false alarm by acting like an Exit 
(OP)/Entry zone. 
When triggered (after arming the system and closing the door or 
opening the door, arming the system, and closing the door), the systemʹs 
Exit Delay time period will be shortened to 3 seconds. 
When you re‐open the door, the entry time restarts. 



ZZ

 

High Temperature

 

 

For detector temperature (hot or cold). This zone operates the same as 24 
hours zone, but it has a special report code.  



ZZ

 

Low Temperature

 

 

For detector temperature (hot or cold). This zone operates the same as 24 
hours zone, but it has a special report code.