Configuring raid network and snmp settings – Grass Valley K2 Storage System Instruction Manual v.3.2 Sep.24 2007 User Manual
Page 633
September 7, 2007
K2 Storage System Instruction Manual
633
Configuring RAID
Configuring RAID network and SNMP settings
Use the Storage Utility to configure the following settings for the Nearline RAID
controller or controllers:
• IP address
• Subnet mask
• Gateway Address
• SNMP trap destinations
For Nearline 10 RAID, network and SNMP settings are set and stored on the RAID
controller module. For the RAID chassis with two controllers, each controller has its
own network settings and the RAID chassis exists as two entities on the control
network.
The RAID storage device is configured by default for the SNMP community name
“public”. If your site’s policies require using a different SNMP community name,
contact your Grass Valley representative.
To configure these settings, do the following:
1. Launch Storage Utility from the K2 System Configuration application as in the
previous procedure.
2. As prompted, wait while Storage Utility gathers system information, then Storage
Utility opens.
3. In Storage Utility tree view, expand the node for the Nearline 10 RAID, right-click
the icon for a Nearline 10 RAID controller, and select
Configuration | Network
Properties
.
The Controller Network Settings dialog box opens.
For a Nearline 10 RAID chassis with two controllers, you can make settings on
both controllers using this dialog box.