K2 Storage System Instruction Manual
September 7, 2007
Chapter 12 Installing the Level 30R Storage System
type the following, then press
Enter
:
snmp-server host public 192.168.40.11
23.Enable Authentication traps. Type the following, then press
Enter
:
snmp-server enable traps authentication
This allows NetCentral to test the switch to verify that it can send its SNMP trap
messages to NetCentral.
24.Type the following, then press
Enter
:
menu
When prompted, save the configuration by pressing the y key. The main menu
opens.
25.If you need a trunk for ISLs to gang switches together, use the following steps.
These steps illustrate trunking the last three 1 Gig ports for three 1 Gig ISLs, which
is the recommended configuration for ISLs on all multi-switch K2 Storage
Systems. Refer to
“Design considerations for Ethernet switches” on page 759
and
consult with your Grass Valley representative if your requirements deviate from
the recommended policy:
a. At the main menu, select
Switch Configuration
and press
Enter
.
b. Choose selection
Port/Trunk Settings
and press
Enter
.
c. Press the right-arrow key to choose
Edit
, then press
Enter
.
d. Down arrow until at the bottom of the list of ports and select the last (highest
port number) 1 Gig port in the list.
e. Right-arrow over to the Group column.
f. Use the Space bar and set the bottom 1 Gig port to
Trk1
.
g. Set the next port up also to
Trk1
.
h. Set the next port up also to
Trk1
.
i. Press
Enter
, then right-arrow to
Save
. Press
Enter
and revert to previous menu.
26.Select
Return to Main Menu
and press
Enter
.
27.From the main menu, tab to
Command Line (CLI)
and press
Enter
. The command
prompt appears.
28.Check the version of firmware currently installed on the switch. Type the
following, then press
Enter
:
show flash
Information is displayed similar to the following example:
HP_iSCSI_switch1# show flash
Image Size(Bytes) Date Version
----- ---------- -------- -------
Primary Image : 3287779 03/15/05 M.08.66
Secondary Image : 3287779 03/15/05 M.08.66