Get Reference:

Gets the reference values of the selected zone for further fault detection. Be aware, the hardware
configuration(IDA8C/S, amplifiers, wiring) should be completed before getting the reference.

Reset Reference:

Clears reference values of the selected zone to return to the initial status. If the reference value
is cleared, monitoring will stop.

Measurement:

After the parameter settings are completed in the grid at the lower part, the IDA8C/S starts to
measure the value received from the internal circuit and displays it on the grid at upper part of
window:

Unloaded Reference:

Displays the value of an unloaded reference which is the gain of an amplifier when there is no
load to the zone. This value is used to determine if there is a fault of a normal amplifier.

Full Loaded Reference:

Displays the value of a fully loaded reference which is the gain of an amplifier when there is a full
load to the zone. This value is used to determine if there is a fault of a normal amplifier.

Measure:

Displays the value of measure, which is the gain of an amplifier.

Faults:

Amplifier Too High:

If Measure > (Unloaded Reference x (100% + Tolerance%)), an Amplifier Too High fault is