Fireman microphone error, Fireman error – ATEIS IDA8 User Manual
Page 113
Product Features
113
© 2012 ATEÏS
If the fault is not solved, replace the Ateis Net card of the IDA8S.
Once it's recovered, the LOG will show:
"Local AteisNet Normal Mode"
4.1.7.1.12 Fireman Microphone Error
Fault Meaning:
Fireman microphone has an error.
Fault Indication:
LED Indicator:
When this error is detected, the following LEDs will light up:
o
G. Fault LED on the front panel of the IDA8C/S.
Log:
o
Fireman Microphone Capsule Open
Text messages display on the touch screen of IDA8C:
"Fireman Error"
"Fireman Audio Open"
A text message displays at the [Machine Fault Record] window in Ateis Studio:
o
Fireman Microphone Capsule Short:
Text messages display on the touch screen of IDA8C:
"Fireman Error"
"Fireman Audio Short"
A text message displays at the [Machine Fault Record] window in Ateis Studio:
o
Fireman Microphone Button Open:
Text messages display on the touch screen of IDA8C:
"Fireman Error"
"Fireman Button Open"