ATEIS IDA8 User Manual
Page 136
ATEIS - IDA8
136
© 2012 ATEÏS
When the window [Monitor(Matrix Mode) - IDA8C/S X] appears, select page [Backup Amplifier
Settings]:
Amplifier:
Indicates which backup amplifier will be monitored.
Line:
Indicates which combination of the zone and the backup amplifier will be monitored.
Tolerance(%):
Determines the boundary of the fault detection for a selected zone. There is a fault recognized if
one of the following conditions is true:
Measure < (Full Loaded Reference x (100% - Tolerance%))
Measure > (Unloaded Reference x (100% + Tolerance%))