Modbus offline, Amp rating fault – ATEIS IDA8 User Manual
Page 121
![background image](https://www.manualsdir.com/files/772583/content/doc121.png)
Product Features
121
© 2012 ATEÏS
Fault Handling
Reload the file.
4.1.7.1.19 ModBus Offline
Fault Meaning:
The Modbus client can't communicate.
Fault Indication:
LED Indicator:
When this error is detected, the following LEDs will light up:
o
G. Fault LED on the front panel of the IDA8C/S.
Log:
Text messages display at the touch screen of the IDA8C:
"ModBus Offline"
Text messages display at the window [Machine Fault Record] in Ateis Studio:
A buzzing sound outputs to the monitoring speaker on the front panel of the IDA8C.
Fault Handling
Check the Modbus client communication. Once it's recovered, the LOG will show:
"ModBus Online."
4.1.7.1.20 AMP Rating Fault
Fault Meaning:
The IDA8 gets the reference value which is too low.
Fault Indication:
LED Indicator:
When this error is detected, the following LEDs will light up:
o
G. Fault LED on the front panel of the IDA8C/S.
Log:
Text messages display at the touch screen of the IDA8C:
"AMP Rating Fault"
"Zone n Normal AMP Rating too low"