beautypg.com

Relay operation, Reflash function, Relay operation -60 reflash function -60 – Yokogawa Standalone MW100 User Manual

Page 74

background image

1-60

IM MW100-01E

Also, when a condition in which alarm output must be cleared arises, you can select
whether to turn output relays OFF (Non-hold), or leave them ON until an output clear
command (alarm ACK) appears (Hold).

Hold operation Notation

Description

Hold

On

Maintains relay output even after relay output is cancelled.

Non-Hold

Off

Does not maintain relay output when relay output is cancelled

(normal operation).

Output cause

occurrence

• When set to non-hold

• When set to hold

Relay output

ON

OFF

Output cause

occurrence

Relay output

ON

OFF

Alarm

ACK

Alarm

ACK

100ms

Relay Operation

The following types of relay operation are available.

Operation Description
And Output ON when all alarms assigned to each alarm output relay activate.
Or

Output ON when one or more alarms assigned to each alarm output relay activate.

Reflash Function

The relay operates after the first alarm. If a second alarm activates, the relay restarts
after briefly stopping operation.
• The non-operation period is 200 ms.
• Even if a new alarm occurs during the non-operation, the non-operation time is not

extended.

• The number of output relays that can be specified for the reflash function is unlimited.
• When selecting relay output other than alarm output relays, the reflash function

specification is disabled.

• You can specify the reflash function when OR is selected for the AND/OR function and

Non-Hold is selected for the Hold/Non-Hold function.

Alarm2 status

Alarm1 status

Alarm3 status

Reflash function

relay status

200ms

200ms

1.14 Functions of the 10-CH, Medium-Speed Digital Output Module