Yokogawa Standalone MW100 User Manual
Page 237
5-24
IM MW100-01E
Input Registers
Data
Data Type
33001
Lower byte of computed data of computation channel A001
Int 32
33002h
Upper byte of computed data of computation channel A001
|
|
33599
Lower byte of computed data of computation channel A300
33600
Upper byte of computed data of computation channel A300
.• No decimal place information
34001
Lower byte of computed data of computation channel A001
Float
34002
Upper byte of computed data of computation channel A001
|
34599
Lower byte of computed data of computation channel A300
34600
Upper byte of computed data of computation channel A300
• Includes decimal place information.
35001
Alarm status of computed data of computation channel A001
Bit string
|
|
35300
Alarm status of computed data of computation channel A300
• Register structure and alarm status value: Same as alarm status of measured data.
36001
Data from measurement channel 001
Int 16
36002
Data from measurement channel 002
|
|
36060
Data from measurement channel 060
• No decimal place information
• Firmware version R3.04or later
37001
Data from MATH channel A001
Int 16
37002
Data from MATH channel A002
|
|
37300
Data from MATH channel A003
• No decimal place information.
• Firmware version R3.04 or later
38001
Measuring
Int 16
38002
Computing
Int 16
38003
Recording
Int 16
38004
Alarm occurring
Int 16
38005
Waiting to confirm alarm status
Int 16
• Input registers indicating mode information are 1 (On) during operation in the relevant
mode, and 0 (Off) when stopped.
• Firmware version R3.03 or later
39001
Year
Int 16
39002
Month
39004
Hours
39005
Minute
39006
Second
39007
Milliseconds
39008
DST(0, 1)
Hold Registers
Data
Data Type
40001
Lower byte of communication input channel C001
Float
40002
Upper byte of communication input channel C001
|
|
40599
Lower byte of communication input channel C300
40600
Upper byte of communication input channel C300
41001
Lower byte of communication input channel C001
Int 32
41002
Upper byte of communication input channel C002
|
|
41599
Lower byte of communication input channel C300
41600
Upper byte of communication input channel C300
• Firmware version R3.04 or later
42001
Communication input channel C001
Int 16
42002
Communication input channel C002
|
|
42300
Communication input channel C300
• Firmware version R3.04 or later
5.2 Main Module (MW100-E) Specifications