beautypg.com

General specifications, External dimensions, General specifications -61 external dimensions -61 – Yokogawa Standalone MW100 User Manual

Page 274: App index

background image

5-61

IM MW100-01E

Specification

1

2

3

4

5

App

Index

5.14 10-CH, Medium-Speed Digital Output Module

(MX125) Specifications

Style number:

S1

Number of outputs:

10

Contact mode:

A contact (SPST)

Update interval:

100 ms minimum (not synchronized to the measurement interval)

Contact capacity:

250 VDC/0.1 A, 250 VAC/2 A, or 30 VDC/2 A (resistance load)

Contact life*:

100,000 times at rated load (typical)

20,000,000 times at no load (typical)

* The contact life varies depending on the load conditions and the

environment in which it is used.

Insulation resistance: Between output terminals and earth terminal: 20 MΩ or more (500

VDC)

Between output terminals: 20 MΩ or more (500 VDC)

Withstand voltage:

2300 VAC (50/60 Hz) for one minute between the output terminal
and earth

2300 VAC (50/60 Hz) for one minute between output terminals

Maximum common-mode voltage:

250 VACrms (50/60 Hz)

Power consumption: Approx. 2 W (when all relays are turned ON)
Terminal type:

Clamp, attached and removed in units of 5 channels

Applicable wire size: 0.08 to 2.5 mm

2

(AWG28 to 12)

External dimensions: Approx. 57 (W) × 131 (H) × 151 (D) mm (including the terminal

cover)

Weight:

Approx. 0.5 kg.

General Specifications

Operating temperature range:

–20 to 50°C

Operating humidity range:

20 to 80% RH for –20 to 40°C

10 to 50% RH for 40 to 50°C

External Dimensions

Units: mm

57

13

1

150.8

If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the
tolerance is ±0.3 mm.