beautypg.com

Communication, Communication -17, App index communication – Yokogawa Standalone MW100 User Manual

Page 230

background image

5-17

IM MW100-01E

Specification

1

2

3

4

5

App

Index

Communication

Ethernet Port

Interface:

Ethernet 10BASE-T/100BASE-TX

The data rate can be fixed to 10 Mbps half duplex by turning
switch 6 of dip switch 1 OFF.

Connector type:

RJ-45

Main protocols:

FTP, SMTP, SNTP, DHCP, DNS, HTTP, Modbus/TCP, and MW100
dedicated protocol.

Communication services: Send/receive measured and computed values, send/receive

setting values, maintenance/diagnostic services, and others.

Login function:

Use when accessing a setting/measurement server, maintenance/
diagnostic server, FTP server, or HTTP server. Up to 10 can be
registered.

List of services:

The port number of each server is the default number.

Server Type

Application

Port Number Number of Simultaneous

Connections

Modbus server

For the Modbus protocol

502

4

FTP server

File transfer service

21

4

HTTP server

Web service

80

Infinity

SNTP server

Adjust the time

123

Infinity

GENE server

For MW100-specific

communication commands

34318

4

DIAG server

For MW100 maintenance

34317

1

EtherNet/IP server

*

EtherNet/IP

44818

10

* Firmware version R3.02 or later

Keep alive function:

If no response is made to periodically sent test packets on the TCP level,

the connection is forcibly closed.

The connection is checked every 30 s. If there is no response, the
connection is checked four times at 5-s intervals. If no response is
received, the connection is disconnected.

Timeout function:

Connection to server from which no communication is made over
a specified period is forcibly dropped.

Server Type

Timeout Value

Modbus server

30 s

FTP server

10 minutes

HTTP server

2 minutes

GENE server

*1

1 to 120 minutes. Set in unit of 1 minute.

DIAG server

10 minutes

EtherNet/IP server

*2

10 minutes

*1 You can select whether to use the timeout function for the GENE server.
*2 Firmware version R3.02 or later

DHCP function:

The IP address is automatically obtained from the DHCP server

5.2 Main Module (MW100-E) Specifications