beautypg.com

Measurement input types, Measurement range, App index – Yokogawa Standalone MW100 User Manual

Page 57

background image

1-43

IM MW100-01E

Explanation of Functions

1

2

3

4

5

App

Index

1.7 Functions of the 6-CH, Medium-Speed Four-

Wire RTD Resistance Input Module

This module allows up to six inputs of DC voltage, 4-wire RTD, 4-wire resistance, and
digital input (DI) at a minimum measurement interval of 100 ms.

Input terminal (clamp terminal)

Terminal cover

Measurement Input Types

Measurement Input Type

Notation

No measurement

SKIP

DC voltage

VOLT

Resistance temperature detector

RTD

Resistance

OHM

DI

DI

Measurement Range

DC Voltage

Measurement Range

Notation

Rated Measurement Range

20 mV

20 mV

–20.000 to 20.000 mV

60 mV

60 mV

–60.00 to 60.00 mV

200 mV

200 mV

–200.00 to 200.00 mV

2 V

2 V

–2.0000 to 2.0000 V

6 V

6 V

–6.000 to 6.000 V

20 V

20 V

–20.000 to 20.000 V

100 V

100 V

–100.00 to 100.00 V

60 mV (high resolution)

60 mVH

0.000 to 60.000 mV

6 V (high resolution)

6 VH

0.0000 to 6.0000 V

1 V

1 V

–1.0000 to 1.0000 V

Resistance Temperature Detector (1 mA)

Measurement Range

Notation

Rated Measurement Range

Pt100

Pt100-1

–200.0 to 600.0°C

JPt100

JPt100-1

–200.0 to 550.0°C

Pt100 (high resolution)

Pt100-1H

–140.00 to 150.00°C

JPt100 (high resolution)

JPt100-1H

–140.00 to 150.00°C

Ni100 SAMA

Ni100SAMA

–200.0 to 250.0°C

Ni100 DIN

Ni100DIN

–60.0 to 180.0°C

Ni120

Ni120

–70.0 to 200.0°C

Pt50

Pt50

–200.0 to 550.0°C

Cu10 GE

Cu10GE

–200.0 to 300.0°C

Cu10 L&N

Cu10LN

–200.0 to 300.0°C

Cu10 WEED

Cu10WEED

–200.0 to 300.0°C

Cu10 BAILEY

Cu10BAILEY

–200.0 to 300.0°C