Measurement input types, Measurement range, App index – Yokogawa Standalone MW100 User Manual
Page 49
1-35
IM MW100-01E
Explanation of Functions
1
2
3
4
5
App
Index
1.4 Functions of the 4-CH, High-Speed Universal
Input Module
This module allows up to four inputs of DC voltage, thermocouple, 3-wire RTD, or digital
input (DI) at a minimum measurement interval of 10 ms.
Input terminal (clamp terminal)
Terminal cover
Measurement Input Types
Measurement Input Type
Notation
Do not measure
SKIP
DC voltage
VOLT
Thermocouple
TC
Resistance temperature detector
RTD
DI
DI
Remote RJC
RRJC
Measurement Range
DC Voltage
Measurement Range
Notation
Rated Measurement Range
20 mV
20 mV
–20.000 to 20.000 mV
60 mV
60 mV
–60.00 to 60.00 mV
200 mV
200 mV
–200.00 to 200.00 mV
2 V
2 V
–2.0000 to 2.0000 V
6 V
6 V
–6.000 to 6.000 V
20 V
20 V
–20.000 to 20.000 V
100 V
100 V
–100.00 to 100.00 V
60 mV (high resolution)
60 mVH
0.000 to 60.000 mV
6 V (high resolution)
6 VH
0.0000 to 6.0000 V
1 V
1 V
–1.0000 to 1.0000 V
Thermocouple
Measurement Range
Notation
Rated Measurement Range
Type-R
R
0.0 to 1760.0°C
Type-S
S
0.0 to 1760.0°C
Type-B
B
0.0 to 1820.0°C
Type-K
K
–200.0 to 1370.0°C
Type-E
E
–200.0 to 800.0°C
Type-J
J
–200.0 to 1100.0°C
Type-T
T
–200.0 to 400.0°C
Type-N
N
0.0 to 1300.0°C
Type-W
W
0.0 to 2315.0°C
Type-L
L
–200.0 to 900.0°C