Appendix 3 Using the Event Action

This section introduces an example in which the event action function is used to save the
data.
• Saving data on the hour
• Acquiring periodic data (periodic report)
• Diving the data on each event

Saving Data on the Hour

Data is saved on the hour by setting the event to Timer and action to Memory Save. In
this example, data is saved at hour 0 using Memory Save.
• Setting the event action
Event: Timer, action: Memory Save, event detection: Edge
• Setting the Recording
Recording start action: Direct, recording stop action: Fullstop or Rotate,

data length: 8 h

• Setting the timer
Timer type: Absolute, Reference time: 0:00, 8 h interval

Time (s)

Division by memory save

Division by the data length

Start

0:00

8:00

16:00

0:00

Stop Start

Acquiring Periodic Data

Create a file containing a single data value by setting the event to Timer and action to
Trigger. This is used to record data periodically (period reporting).
• Setting the event action
Event: Timer, action: Trigger, event detection: Edge
• Setting the Recording
Recording start action: Trigger (pretrigger 100%), measurement interval: 1 min,

recording interval: 10x

Recording stop action: Fullstop or Rotate, data length: 10 min
• Setting the timer
Timer type: Absolute, Reference time: 0:00, 1 h interval

Time (s)

File containing a single data value

Start

1:00

Trigger

2:00

3:00

4:00

Stop Start

In the recording interval setting above, one data value is recorded every 10 minutes. To
record the data to the file on the hour, start the recording at 0:00, 0:10, 0:20 and so on (at
any of the 10 minute intervals). If you start the recording at 0:03, the data is recorded at
0:53, 1:53, 2:53, and so on.