beautypg.com

Wiring the 4-wire rtd resistance input module, Wiring the strain input module, App index – Yokogawa Standalone MW100 User Manual

Page 101

background image

2-13

IM MW100-01E

Installation and W

iring

1

2

3

4

5

App

Index

2.4 Connecting Signal Wires

Wiring the 4-Wire RTD Resistance Input Module

Voltage

Nothing connected to

the I or C terminal

Resistance, RTD

+

Resistance per lead wire of 10 Ω or less

DC voltage

Input

Contact

• DC voltage input/DI (contact) input

• RTD input, resistance input

• DC current input

DC current input

Shunt resistor

Example: For 4 to 20 mA input, shut resistance values

should be 250 Ω ±0.1%.

+

C

A

B

I

C

A

B

I

C

A

B

I

Terminal type:

Clamp

Applicable wire size:

0.14 to 1.5 mm

2

(AWG26 to 16)

Wiring the Strain Input Module

Note

When using a sensor without a remote sensing wire, use the DV450-001 (conversion cable).

• 1 Gauge Method

Setting switch

ON

OFF

No.1

No.2

No.3

No.4

No.5

A(+V)

B( L)

C(-V)

D( H)

-B12, -B35

E

e

Rg

R

R

R

Rg

No.1

ON

No.2

ON

No.3

ON

No.4

OFF

No.5

OFF

Rg

R: fixed resistance

r: resistance value of lead

wire

Rg: resistance value of strain

gauge

e: output voltage from bridge

E: voltage applied to bridge

Setting

switch

-NDI

Rg

ON

1 2 3 4 5

1

2

3

4

5

6

7

8

OFF
SW

Bridge head

(701955 or 701956)

SW1

ON

SW2

ON

SW3

ON

SW4

ON

SW5

OFF