5-44

IM MW100-01E

Measurement Interval, Integration Time, and Filter:

Measurement

Interval

500 ms

16.67 ms
20 ms
Auto

*2

Integration

Time

Filter

Rejected Noise and Notes

1 s

Rectangular

2 s

5 s

10, 20, 30, 60 s

36.67 ms

*3

100 ms

*4

100 ms

Trapezoidal
Rectangular

600 Hz and its integer multiples

*1

60 Hz and its integer multiples
50 Hz and its integer multiples

Automatically detects the power supply frequency and set

16.67 or 20 ms

50 Hz or 60 Hz and their integer multiples
10 Hz and its integer multiples

Burnout

Detection

Cycle

1.67 ms

Measurement

interval

*1 Because the power supply frequency noise is not rejected, the measured vales may fluctuate especially with

temperature measurement using thermocouples. In such cases, increase the measurement interval, or use

the 4-CH High-Speed Universal Input Module or the 10-CH, Medium Speed Universal Input Module.

*2 For DC power, set to 20 ms.

*3 When synchronizing time by SNTP, the integral time is the same as when the measurement interval is 1 s.

*4 When synchronizing time by SNTP, the integral time is set to 36.67 ms. Also in this case, noise of 50 Hz, 60

Hz, and their integer multiples is rejected.

Reference junction compensation:

Switch external/internal by channel, includes remote RJC function

Reference junction compensation accuracy:

When measuring temperature greater than or equal to 0 °C and
when the temperature of the input terminal is balanced

Type R, S, W: ±1°C

Type K, J, E, T, N, L, U, XK GOST: ±0.5°C

Type N (AWG14), PLATINEL, NiNiMo, WRe3-25, W/WRe26: ±1°C

Note: Type B and PR40-20 internal RJC is fixed at 0°C

Maximum input voltage: DC voltage at 1-V range or less, TC, and DI (contact): ±10 VDC

(continuous)

Other measurement ranges: ±120 VDC (continuous)

Normal-mode voltage: DC voltage, TC, DI (LEVEL): 1.2 times the range rating or less

(50/60 Hz, peak value including the signal component)

Normal-mode rejection ratio:

For integration time of 16.67 ms or more: 40 dB or more (50/60
Hz ± 0.1%)

For integration time of 1.67 ms: 50/60 Hz is not rejected.

Common-mode voltage: 600 VACrms (50/60 Hz), reinforced (double) insulation
Common mode rejection ratio:

When the integration time is 16.67 ms or more: 120 dB or more

When the integration time is 1.67 ms: 80 dB or more

(50/60 Hz ±0.1%, 500 Ω unbalanced between minus
measurement terminal and ground)

Common-mode voltage between channels: 120 VACrms (50/60 Hz)
Noise rejection:

Rejection by the integrating A/D converter and the use of low pass
filters

Input resistance:

For DC voltage 1 V range or less and thermocouple range: 10 MΩ
or less

For DC voltage 2 V range or higher: Approx. 1 MΩ

Insulation resistance: Between input and ground: 20 MΩ or more (500 VDC)
Input bias current:

10 nA or less (except for burnout setting)

Withstand Voltage:

1000 VAC (50/60 Hz) for one minute between input terminals
3700 VAC (50/60 Hz) for one minute between the input terminal
and earth terminal

Input signal source resistance:

DC voltage, thermocouple: 2 kΩ or less

Thermocouple burnout: Detection at a specifi ed detection interval per measurement

interval and detection within the thermocouple range (detection
ON/OFF possible)

5.6 30-CH, Medium-Speed DCV/TC/DI Input Module (MX110-VTD-L30) Specifications