General specifications, External dimensions, General specifications -54 external dimensions -54 – Yokogawa Standalone MW100 User Manual
Page 267
5-54
IM MW100-01E
Contact/transistor rating:
Contact with a rating of 15 VDC or more, and 30 mA or more
Transistor with a rating of Vce > 15, and Ic > 30 mA
Maximum input voltage: ± 10 V
Insulating resistance: Input terminals to ground: 20 MΩ or more (500 VDC)
Withstand voltage:
Input terminal to ground: 2300 VAC (50/60 Hz), for one minute
Maximum common mode voltage:
250 VACrms (50/60 Hz)
Terminal type:
Clamp
Power consumption: Approx. 1.5 W
Applicable wire size: 0.14 to 1.5 mm
2
(AWG26 to 16)
External dimensions: Approx. 57 (W) × 131 (H) × 151 (D) mm (including terminal cover)
Weight:
Approx. 0.5 kg.
General Specifications
Operating temperature range:
–20 to 60°C
Operating humidity range:
20 to 80% RH for –20 to 40°C
10 to 50% RH for 40 to 50°C
5 to 30% RH for 50 to 60°C
External Dimensions
Units: mm
57
13
1
150.8
If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the
tolerance is ±0.3 mm.