Effects of operating conditions, General specifications, External dimensions – Yokogawa Standalone MW100 User Manual
Page 251
5-38
IM MW100-01E
Effects of Operating Conditions
The specifications below apply when the integration time is 16.67 ms or more.
Warm-up time:
At least 30 minutes after power-up
Effects of ambient temperature:
The effect received by changes in 10°C increments of the ambient
temperature is
±(0.05% of rdg. + 0.05% of range) or less
However, for Cu10 Ω: ±(0.2% of range + 1 digit)
Effects of power fluctuation:
Meets the accuracy specifications for AC power supply in the
range 90 to 132 V and 180 to 250 V
Effects of magnetic field: The fluctuation in external magnetic fields for AC (50/60 Hz)
400 A/m is
±(0.1% of rdg. + 10 digits) or less
Effects from the signal source resistance:
Effect from fluctuation in DC voltage and thermocouple signal
source resistance of 1 kΩ
DC voltage:
1 V range or less
±10 µV or less
2 V range or higher ±0.15% of rdg. or less
Thermocouple: ±10 µV or less
However, when burnout is set, ±150 µV or less
RTD:
Fluctuation per 10 Ω change per line (3 lines all
same resistance) for 100 Ω types: ±0.1°C or less;
other than 100 Ω types: ±1.0°C or less; fluctuation
resulting from difference in resistance between
lead wires of 40 mΩ (max. difference among
three wires): approximately 0.1°C (for Pt100)
Effect of position:
Horizontal with the feet at the bottom is the rule.
Effects of vibration:
The fluctuation that results by applying a sinusoidal vibration
along all three axes at a frequency between 10 to 60 Hz and an
acceleration of 0.2 m/s
2
is ±(0.1% of rdg. + 1 digit) or less
General Specifications
Operating temperature range: –20 to 60°C
Operating humidity range: 20 to 80% RH for –20 to 40°C
10 to 50% RH for 40 to 50°C
5 to 30% RH for 50 to 60°C
External Dimensions
Units: mm
150.8
57
131
If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the
tolerance is ±0.3 mm.
5.4 4-CH, High-Speed Universal Input Module (MX110-UNV-H04) Specifications