beautypg.com

Turning the power switch on and off, Turning the power switch on and off -23, App index – Yokogawa Standalone MW100 User Manual

Page 111: Warning

background image

2-23

IM MW100-01E

Installation and W

iring

1

2

3

4

5

App

Index

When Using a DC Power Supply

WARNING

• To prevent the possibility of electric shock when wiring, confirm that the power

supply source is turned OFF.

• To avoid electric shock or fire, use electric wires having a cross sectional area of

0.3 mm2 (AWG 22) or more.

1.

Check that the power supply and the power switch of the main module is OFF.

2.

Loosen the screw fixing the power supply terminal cover of the main module in

place and open the power supply terminal cover.

3.

Following the wiring diagram (see “When Using an AC Adapter” in this section),

wire the plus/minus wires from the DC power supply and the protective grounding
wire to the power supply terminal.

4.

Close the power supply terminal cover and secure it with the screw.

Use a power supply that meets the conditions indicated below.

Item

Specifications

Rated supply voltage

12 to 28 VDC

Supply voltage range used

DC power supply: 10 to 32 VDC

Maximum power consumption Up to approximately 35 VA maximum when six modules are

used

Turning the Power Switch ON and OFF

Pressing the “I” side of the power switch turns the instrument ON. Pressing the “O” side
turns the instrument OFF.
When turned ON, the 7-segment LED (see section 1.3, “Functions of the Main Module”
illuminates. When the self check and other processes are complete, the unit number is
displayed.

Note

• Before turning the power ON, check that the modules are attached correctly and that the

power cord is connected correctly.

• If the 7-segment LED does not illuminate even if the power switch is turned ON, turn OFF

the power switch, then check the items below. If the condition does not change when turning
ON the power even after checking those items, it is probably a malfunction. Contact your
nearest YOKOGAWA dealer for repairs.
• That the power cord is plugged in properly.
• That the power supply voltage is within the allowable voltage range specified in this

section

• If the 7-segment LED displays something other than a unit number when the power switch

is turned ON, see section 4.1, “Error Display on the 7-Segment LED and Corrective Actions”
and carry out the specified corrective action. If the displayed information does not change
even when you carry out the corrective action, it is probably a malfunction. Contact your
nearest YOKOGAWA dealer for repairs.

2.5 Connecting the Power Supply and Turning the Power Switch ON and OFF