Input range, Input threshold level, Filter – Yokogawa Standalone MW100 User Manual

Page 64: Integration

background image

1-50

IM MW100-01E

Input Range

Maximum speed: 10000 pulses/s
Minimum input pulse width: 40 μs

Input Threshold Level

LEVEL

Counts when changing from 1 V or less to 3 V or more

Contact input

Count upon change from contact open to contact close
Contact open: 100 kΩ or more
Contact close: 100 Ω or less

Filter

Anti-Noise Filter

The integral time and types of filters applied vary depending on the measurement
interval.

For information on filters, see section 2.9, “Measures Against Noise on the MW100 Data

Acquisition Unit.”

Chattering Filter

Removes chattering of up to 5 ms (can be turned ON/OFF on individual channels)
Turn the chattering filter OFF when measuring on circuits with no chattering.

Integration

The measured values from the 10-CH Pulse Input Module are reset every measurement
intervals by the pulse integral value of each measurement interval. Continued pulse
integration is carried out with the pulse integration (TLOG.PSUM) by the MW100 main
module’s integration function.
Even if the MATH function (/M1 option) is not included, channels included on the 10-CH
Pulse Input Module are only available for integration (TLOG.PSUM).

MATH Function

(/M1 Option)

10-CH Pulse

Input Module

MATH Function

(See Section 1.15) Limitation

Yes

None

Available

No

No

Included

Operator: Only TLOG.PSUM() can be used

Computation channels: A001 to A060

Broken-line input channel function: Not

available

Long-duration moving average function: Not

available

Modbus master function: Not available

Modbus client function: Not available

Not included

Not available

None

1.9 Functions of the 10-CH, Pulse Input Module