Input range, Input threshold level, Filter – Yokogawa Standalone MW100 User Manual
Page 64: Integration
1-50
IM MW100-01E
Input Range
Maximum speed: 10000 pulses/s
Minimum input pulse width: 40 μs
Input Threshold Level
LEVEL
Counts when changing from 1 V or less to 3 V or more
Contact input
Count upon change from contact open to contact close
Contact open: 100 kΩ or more
Contact close: 100 Ω or less
Filter
Anti-Noise Filter
The integral time and types of filters applied vary depending on the measurement
interval.
For information on filters, see section 2.9, “Measures Against Noise on the MW100 Data
Acquisition Unit.”
Chattering Filter
Removes chattering of up to 5 ms (can be turned ON/OFF on individual channels)
Turn the chattering filter OFF when measuring on circuits with no chattering.
Integration
The measured values from the 10-CH Pulse Input Module are reset every measurement
intervals by the pulse integral value of each measurement interval. Continued pulse
integration is carried out with the pulse integration (TLOG.PSUM) by the MW100 main
module’s integration function.
Even if the MATH function (/M1 option) is not included, channels included on the 10-CH
Pulse Input Module are only available for integration (TLOG.PSUM).
MATH Function
(/M1 Option)
10-CH Pulse
Input Module
MATH Function
(See Section 1.15) Limitation
Yes
None
Available
No
No
Included
Operator: Only TLOG.PSUM() can be used
Computation channels: A001 to A060
Broken-line input channel function: Not
available
Long-duration moving average function: Not
available
Modbus master function: Not available
Modbus client function: Not available
Not included
Not available
None
1.9 Functions of the 10-CH, Pulse Input Module