beautypg.com

Daylight saving time setting, Other settings – Yokogawa Standalone MW100 User Manual

Page 138

background image

3-16

IM MW100-01E

Daylight Saving Time Setting

1.

From the top screen, click

System Setting > Daylight Saving Time Setting.

2.

Select the

Daylight Saving Time check box. The Summer time and Winter time

function is enabled.

3.

Select a starting month, week, and day of the week for the start of Summer time

in the

Start Time box. Enter a start time in the box.

4.

Select an ending month, week, and day of the week for the end of Summer time

in the

End Time box. Enter an end time in the box.

5.

Click the

Apply button. The Summer time and Winter time start times are enabled.

Other Settings

This is for entering the MW100 unit number, units of temperature, alarm hold, rate-of-
change interval, and strain initial balance settings.

From the top screen, click

System Setting > Other Settings.

Unit Number

1.

Enter a number from 0 to 89 for identifying the MW100 unit in the

Unit No. box.

2.

Click the

Apply button. This enables the setting changes.

Temperature Unit

1.

Select Celsius

deg C or Fahrenheit deg F in the Temperature Unit list.

2.

Click the

Apply button. This enables the setting changes.

Alarm Status Hold

1.

If the

Hold check box is selected, alarms are held.

2.

Click the

Apply button. This enables the setting changes.

For a description of the alarm hold/non-hold, see “Alarms” in section 1.3.

Rate-of-Change Interval

1.

Enter the measurement count that determines the interval in the

Increase

Interval box under Rate-of-Change Alarm.

2.

Enter the measurement count that determines the interval in the

Decrease

Interval box under Rate-of-Change Alarm.

3.

Click the

Apply button. The settings for each item are applied.

For a description of the rate-of-change interval, see “Alarms” in section 1.3.

3.3 System Settings