beautypg.com

Wiring with the digital output module, Wiring with the digital output module -19 – Yokogawa Standalone MW100 User Manual

Page 107

background image

2-19

IM MW100-01E

Installation and W

iring

1

2

3

4

5

App

Index

Wiring with the Digital Output Module

C

NO

250 VDC/0.1 A, 250 VAC/2 A, or

30 VDC/2 A (resistance load)

Main Output Specifications

Contact mode: A contact (SPST)
Contact capacity: 250 VDC/0.1 A, 250 VAC/2 A, or 30 VDC/2 A (resistance load)
Terminal type: Clamp, attached and removed in units of 5 channels
Applicable wire size: 0.08 to 2.5 mm

2

(AWG28 to 12)

Note

Do not connect anything to the unassigned terminals of the digital output module.

2.4 Connecting Signal Wires