3.7 Setting Alarms
You can set the alarm type, alarm value, hysteresis, and output operation. Only the alarm
value can be changed while the recording is in progress.
For a description of alarm types, see “Alarms” in section 1.3.
Setting Mode
Meas. Mode
Alarm Setting (AI/DI)
You can set measurement channel alarms.
1.
From the top screen, click
Channel Setting > Alarm Setting (AI/DI).
2.
Select the channel group you wish to set from the
Channel List list.
Alarm Settings
3.
Select the alarm type from the
Level list.
To use the upper (rH) or lower (rL) limit on rate-of-change alarm, you must set the rate-of-
change interval.
To use the delay upper (tH) or lower (tL) limit alarm, you must set the delay alarm.
4.
Enter an alarm value in the
Value box.
5.
Enter a hysteresis value in the
Hysteresis box.
For the procedure to set the rate-of-change interval, see “Other Settings” in section 3.3.
For the procedure to set the delay alarm, see “Delay Alarm Setting” in this section.
Output Settings
6.
Turn output On/Off in the
Action box.
7.
Enter an alarm output channel in the
Relay box.
8.
Click the
Apply button. The setting changes take effect.