beautypg.com

Steady output operation, Steady output operation -56, Output operation when connected for communication – Yokogawa Standalone MW100 User Manual

Page 70

background image

1-56

IM MW100-01E

Steady Output Operation

Output Operation When Connected for Communication

Communication Connection Status

Output Operation

Normal connection (initial connection after power ON) Operation when power is turned ON
Communications opened successfully

Holds the output value (last output value)

(when communications were cut and restored for the 2nd or more time)
Communication disconnected successfully

Holds the output value (last output value)

Output Operation during Measurement and When Performing Transmission
Output

“Transmission output execution ON” in the table is when the transmission output control
is ON. “Transmission output execution OFF” in the table is when the transmission output
control is OFF.
The status of transmission output execution below is for transmission output on
measurement channels. For transmission on MATH channels, substitute “measurement
start” with “computation start,” “measurement stop” with “computation stop,” and
“measuring” with “computing.”

Output Setup

Status

Output Operation

Transmission

output within unit

Meas. stop →

Measurement starts

Transmission output start or output value hold (depending

on the transmission output execution on/off status

on: transmission output starts

off: output value held)

Measuring →

Measurement stops

Depending on the output operation upon stop setting

Last: Holds the output value (last output value)

Preset: Outputs the preset value

*

Measuring

Transmission output

execution off → on

Transmission start

Transmission output

execution on → off

Holds output value (last output value)

Arbitrary output

Meas. stop →

Measurement start

No effect

Measuring →

Measurement stop

No effect

Measuring

Transmission output

execution off → on

No effect

Transmission output

execution on → off

No effect

* Firmware version R3.03 or later

1.13 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output

Module