2-30

IM MW100-01E

2.9 Measures Against Noise on the MW100 Data

Acquisition Unit

The technical Information described below is available as reference material on
measures against noise. For information on obtaining a copy, contact your nearest
YOKOGAWA dealer.
• Noise Interference on Recorder (TI 4D5B1-80E)
Describes the fundamentals concerning noise and its countermeasures in two parts:

basic edition and application edition.

• MX100 Performance Specifications (TI 04M08B01-00E)
This describes in detail the noise rejection characteristics and functions that are

unique to the MW100 Data Acquisition Unit.

This section briefly describes the integrating A/D converter and the first-order lag filter
that the MW100 Data Acquisition Unit employs as measures against noise.

Integrating A/D Converter

MW100 input modules employ integrating A/D converters for converting the measured
analog signals into digital signals. The integrating A/D converter integrates the measured
values at the specified time width. If the specified time width matches the period of the
signal you wish to reject, the signal is rejected.

Cancelled out

Integration time

DC voltage (average value)

Input voltage

(instantaneous value)

For example, if the integration time is 20 ms, signals having frequencies of 50 Hz and
integer multiples of 50 Hz can be rejected. Likewise, if the integration time is 16.67 ms,
signals having frequencies of 60 Hz and integer multiples of 60 Hz can be rejected. If
the integration time is 100 ms, signals having 10 Hz and integer multiples of 10 Hz can
be rejected. The commercial power supply is one of the noise sources. By setting these
integration times, commercial power noise of 50 Hz or 60 Hz can be eliminated.
On the MW100, the integration time is set as shown below.

Measurement

Interval

10 ms

1.67 ms

16.67 ms

20 ms

Auto

Integration

Time

Rejected Frequencies and Notes

50 ms

100 ms

200 ms

500 ms

1 s

2, 5,10, 20, 30, 60 s

36.67 ms
100 ms
200 ms

600 Hz and its integer multiples

60 Hz and its integer multiples
50 Hz and its integer multiples

Automatically detects the power supply frequency and set 16.67 or 20 ms
50 Hz and 60 Hz and their integer multiples
10 Hz and its integer multiples

Low-pass filter with Fc = 5 Hz

4-CH, High-Speed Universal Input Module

* Because the power supply frequency noise is not rejected, measured values may fluctuate particularly in temperature

measurements. If this happens, make the measurement interval longer.