External Dimensions

Units: mm

57

13

1

150.8

If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the
tolerance is ±0.3 mm.

Output Span Setting

Limit value of V mode and mA mode
Modes Output

Setting span

Setting span

Output

lower limit

*1

lower limit

upper limit

upper limit

*2

V mode –11[V]

–10[V]

+10[V]

+11[V]

mA mode 0[mA]

0[mA]

20[mA]

22[mA]

*1 –OVER, preset value
*2 + OVER, preset value

Handling Abnormal Data

Abnormal Data Types

Output value

Data upon startup

Preset value or previously held value can be selected

Data upon error occurrence

Preset value or previously held value can be selected

+OVER

5% of output Full Span

–OVER

–5% of output Full Span

±OVER conditions
• When the input channel is ±OVER in the case of transmission output
• When outside the range of voltage –11 V to +11 V, or current 0 mA to 22 mA (accuracy

assured at 1 mA or more)

5.11 8-CH, Medium-Speed Analog Output Module (MX120-VAO-M08) Specifications