Program channel settings, Rolling average settings, App index program channel settings – Yokogawa Standalone MW100 User Manual
Page 153
3-31
IM MW100-01E
Setting and Data acquisition
1
2
3
4
5
App
Index
Program Channel Settings
1.
From the top screen, click
Channel Setting > Program Channel Setting.
2.
Select Single or Repeat in the
Action box for the program channel number you
wish to use.
3.
Enter the elapsed time and setting value in the
Point Set box.
4.
Click the
Apply button. The setting changes take effect.
For a description of the syntax of broken line data, see “Reference Channels” in section 1.15.
For a description of the broken line data, see appendix 7, “Using the Broken Line Data.”
Rolling Average Settings
1.
From the top screen, click
Channel Settings > Rolling Average Setting under
the Top item.
2.
Select the channel group you wish to set from the
Channel List list.
3.
In the
Action list, select On to enable the long term moving average, or Off to
disable it.
4.
Select the sampling interval from the
Interval list.
Set a multiple of the MATH interval.
5.
Enter the number of samples for the moving average in the
Number of samples
box.
6.
Click the
Apply button. This enables the settings changes.
For information on rolling averages see “Rolling Average” in section 1.15.