Register Assign (Modbus Server Functions and Sharing)
Coil
*
Data
Data type
00001
Data on communication input channel C001
Bit
00002
Data on communication input channel C002
Bit
|
|
|
00300
Data on communication input channel C300
Bit
Communication input channel coils are 0 (Off) when data is zero, infinite (+Inf, –Inf), or
NaN, and 1 (On) when data is one or non-infinite.
* Firmware version R3.03 or later
Input Relay
*
Data
Data type
10001
Data on measurement channel 001
Bit
10002
Data on measurement channel 002
Bit
|
|
|
10060
Data on measurement channel 060
Bit
Input relays of measurement channels are 0 (Off) when data is zero, infinite or of a special
value (+Over, –Over, Skip, No Channel, Error, Invalid, or Lack), and 1 (On) when data is
one or non-infinite.
13001
Data on MATH channel A001
Bit
13002
Data on MATH channel A002
Bit
|
|
|
13300
Data on MATH channel A300
Bit
Input relays of MATH channels are 0 (Off) when data is zero, infinite or of a special value
(+Over, –Over, Skip, No Channel, Error, Invalid, or Lack), and 1 (On) when data is one or
non-infinite.
18001
Measuring
Bit
18002
Computing
Bit
18003
Recording
Bit
18004
Alarm occurring
Bit
18005
Waiting to confirm alarm status
Bit
Input relays indicating mode information are 1 (On) during operation in the relevant mode,
and 0 (Off) when stopped.
* Firmware version R3.03 or later
Input Registers
Data
Data Type
30001
Lower byte of measured data of measurement channel 001
Int 32
30002
Upper byte of measured data of measurement channel 001
|
|
30119
Lower byte of measured data from measurement channel 060
30120
Upper byte of measured data from measurement channel 060
• No decimal place information
31001
Lower byte of measured data from measurement channel 001
Float
31002
Upper byte of measured data from measurement channel 001
|
|
31119
Lower byte of measured data from measurement channel 060
31120
Upper byte of measured data from measurement channel 060
• Includes decimal place information.
32001
Alarm status of measured data of measurement channel 001
Bit string
|
|
32060
Alarm status of measured data of measurement channel 060
• Register structure and alarm status values
Alarm
2
1
4
3
4 bits
4 bits 4 bits 4 bits
0: No alarms
2: Lower limit alarm occurs
4: Differential lower limit alarm occurs
6: Lower limit on rate-of-change alarm occurs
8: Delay lower limit alarm occurs
1: Upper limit alarm occurs
3: Differential upper limit alarm occurs
5: Upper limit on rate-of-change alarm occurs
7: Delay upper limit alarm occurs