5.10 10-CH, High-Speed Digital Input Module

(MX115) Specifications

Style number:

S1(-D05), S2(-D24)

Input type:

-D05: Contact (non-voltage contact, open collector) and LEVEL

(5-V logic)

-D24: LEVEL (24-V logic)

Number of inputs:

10

Input format:

-D05: Pull up at approx. 5 V/approx. 5 kΩ, non-isolated

between channels

-D24: No isolation between channels

Measurement interval: Select 10 ms, 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10

s, 20 s, 30 s, or 60 s

Filter

Measurement interval of 5 s or less: Use the wider of the ON/

OFF width of the detection period (approximately 75% to 90%

of the measurement interval)

Measurement interval of 5 s or more: Use the wider of the ON/

OFF width of approximately 4.5 s

Minimum detection pulse width: Twice the sampling interval or more

Input threshold level: -D05: Contact (non-voltage contact, open collector):

100 Ω or less, ON, 100 kΩ or more, OFF

LEVEL (5-V logic): OFF at 1 V or less and ON at 3 V or more

-D24: LEVEL (24-V logic): OFF at 6 V or less and ON at 16 V

or greater

Hysteresis width:

-D05: Approx. 0.1 V

-D24: Approx. 1.5 V

Contact transistor rating: 15 VDC or greater and 30 mA or greater

Transistor with a rating of Vce > 15 VDC and Ic > 30 mA

Maximum input voltage: -D05: ±10 V

-D24: ±50 V

Insulation resistance: Between input terminals and ground: 20 MΩ or more (500

VDC)

Withstand voltage:

2300 VAC (50/60 Hz) for one minute between input and earth

Maximum common mode voltage: 250 VACrms (50/60 Hz)

Terminal type:

Clamp

Power consumption: Approx. 1.5 W

Applicable wire size: 0.14 to 1.5 mm

2

(AWG26 to 16)

External dimensions: Approx. 57 (W) × 131 (H) × 151 (D) mm (including the terminal

cover)

Weight:

Approx. 0.5 kg.

General Specifications

Operating temperature range:

–20 to 60°C

Operating humidity range:

20 to 80% RH for –20 to 40°C

10 to 50% RH for 40 to 50°C

5 to 30% RH for 50 to 60°C

External Dimensions

Units: mm

57

13

1

150.8

If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the

tolerance is ±0.3 mm.