App index – Yokogawa Standalone MW100 User Manual
Page 248
5-35
IM MW100-01E
Specification
1
2
3
4
5
App
Index
5.4 4-CH, High-Speed Universal Input Module
(MX110-UNV-H04) Specifications
Style number:
S1
Type of measurement: DC voltage, thermocouple, 3-wire RTD, DI (contact, LEVEL)
Number of inputs:
4
Input method:
Floating unbalanced input, insulation between channels
A/D resolution:
16 bits (±20000/±6000/0 to 60000)
Measurement range and accuracy:
The accuracy applies to standard operating conditions:
Ambient temp: 23 ±2°C, ambient humidity: 55 ±10% RH, supply
voltage: 90 to 250 VAC, power frequency: 50/60 Hz ±1%, warm-
up time: at least 30 minutes, without adverse conditions such as
vibrations.
Input
DC voltage
20 mV
60 mV
200 mV
2 V
6 V
20 V
100 V
60 mV (high res.)
6 V (high res.)
1 V
R
*1
S
*1
B
*1
K
*1
E
*1
J
*1
T
*1
L
*2
U
N
*3
W
*4
KPvsAu7Fe
PR40-20
NiNiMo
WRe3-25
W/WRe26
N (AWG14)
XK GOST
–20.000 to 20.000 mV
–60.00 to 60.00 mV
–200.00 to 200.00 mV
–2.0000 to 2.0000 V
–6.000 to 6.000 V
–20.000 to 20.000 V
–100.00 to 100.00 V
0.000 to 60.000 mV
0.0000 to 6.0000 V
–1.0000 to 1.0000 V
0.0 to 1760.0°C
0.0 to 1820.0°C
–200.0 to 1370.0°C
–200.0 to 800.0°C
–200.0 to 1100.0°C
–200.0 to 400.0°C
–200.0 to 900.0°C
–200.0 to 400.0°C
0.0 to 1300.0°C
0.0 to 2315.0°C
0.0 to 300.0K
0.0 to 1900.0°C
0.0 to 1310.0°C
0.0 to 2400.0°C
0.0 to 2400.0°C
0.0 to 1300.0°C
–200.0 to 600.0°C
Measurement Accuracy
Integration Time: 16.67 ms
or More
Highest
Resolution
(1 Digit)
±(0.05% of rdg + 5 digits)
±(0.05% of rdg + 2 digits)
±(0.05% of rdg + 2 digits)
±(0.05% of rdg + 5 digits)
±(0.05% of rdg + 2 digits)
±(0.05% of rdg + 2 digits)
±(0.05% of rdg + 2 digits)
±(0.05% of rdg + 20 digits)
±(0.05% of rdg + 20 digits)
±(0.05% of rdg + 2 digits)
±(0.05% of rdg + 1°C)
Except 0 to 100°C: 3.7°C, 100 to
300°C: 1.5°C for R and S;
400 to 600°C: 2°C, less than
400°C: not guaranteed for B
±(0.05% of rdg + 0.7°C)
Except –200°C to –100°C:
±(0.05% of rdg + 1°C)
±(0.05% of rdg + 0.5°C)
Except –200°C to –100°C:
±(0.05% of rdg + 0.7°C) for J and L
±(0.05% of rdg + 0.7°C)
±(0.05% of rdg + 1°C)
±(0.05% of rdg + 0.7K)
±(0.05% of rdg + 2.5°C)
Except 300 to 700°C: 6°C,
less than 300°C: not guaranteed
±(0.05% of rdg + 0.7°C)
±(0.05% of rdg + 2°C)
Except 0 to 200°C: 2.5°C,
more than 2000°C:
±(0.05% of rdg + 4°C)
±(0.05% of rdg + 2°C)
Except 100 to 300°C: 4°C,
less than 100°C: not guaranteed
±(0.05% of rdg + 0.7°C)
±(0.05% of rdg + 0.5°C)
Except –200 to 0°C:
±(0.2% of rdg + 0.7°C)
Rated
Measurement
Range
1 µV
10 µV
10 µV
100 µV
1 mV
1 mV
10 mV
1 µV
100 µV
100 µV
0.1°C
0.1K
0.1°C
*1 R, S, B, K, E, J, T: ANSI, IEC 584, DIN IEC 584, JIS C 1602-1995
*2 L: Fe-CuNi, DIN43710/U: Cu-CuNi, DIN 43710
*3 N: Nicrosil-Nisil, IEC 584, DIN IEC 584
*4 W: W-5% Re/W-26%Re (Hoskins Mfg Co)
Thermocouple (excludes RJC accuracy
, when burnout
is OFF)
Measurement Accuracy
Integration Time: 1.67 ms
±(0.1% of rdg + 25digits)
±(0.1% of rdg + 10digits)
±(0.1% of rdg + 100 digits)
±(0.1% of rdg + 100 digits)
±(0.1% of rdg + 10 digits)
±(0.1% of rdg + 4°C)
Except 0 to 100°C: 10°C, 100 to
300°C: 5°C for R and S;
400 to 600°C: 7°C, less than
400°C: not guaranteed for B
±(0.1% of rdg + 3.5°C)
Except –200°C to –100°C:
±(0.1% of rdg + 6°C)
±(0.1% of rdg + 2.5°C)
Except –200°C to –100°C:
±(0.1% of rdg + 5°C) for J and L
±(0.1% of rdg + 3.5°C)
±(0.1% of rdg + 7°C)
±(0.1% of rdg + 3.5K)
±(0.1% of rdg + 12°C)
Except 300 to 700°C: 25°C,
less than 300°C: not guaranteed
±(0.1% of rdg + 2.7°C)
±(0.1% of rdg + 7°C)
Except 0 to 200°C: 12°C,
more than 2000°C:
±(0.1% of rdg + 11°C)
±(0.1% of rdg + 8.5°C)
Except 100 to 300°C: 12°C,
less than 100°C: not guaranteed
±(0.1% of rdg + 3.5°C)
±(0.1% of rdg + 2.5°C)
Except –200 to 0°C:
±(1% of rdg + 2.5°C)
Measurement
Range
Type